¾" Copper/Aluminum
Single element Panel-Trim AAA-3 hot water ratings BTU per hour per linear foot of active
(finned) length.
AVERAGE WATER TEMPERATURE
Degrees F
150°
160°
170°
180°
190°
200°
210°
220°
Rated Capacity
1GPM
480
570
650
740
820
910
990
1080
4GPM
510
600
690
780
870
960
1050
1140
The use of I=B=R Rating @ 4GPM is limited to installations where flow rate is known
to be equal to or greater than 4 GPM. If flow rate is unknown, use 1 GPM rating
· I=B=R Ratings include 15% addition to water heat capacity
· Hot water ratings shown are at the STANDARD WATER FLOW
RATE of 500 lbs/hr (1GPM) and 2,000 lbs/hr (4 GPM) with 65° entering air temperature
· Friction loss through Argo Baseboard unit at 1 GPM (500 lbs/hr)
is 47 MIL-INCHES per foot and at 4 GPM (2000 lbs/hr) is 525 MIL-INCHES PER FOOT
· Ratings based on active length. Difference between active and
total length is approximately 2". Aluminum fins are 2-1/8" x 2-¾"
x .008" thick, spaced 60 per foot (unpainted)
· All hot water ratings shown in this table determined in
conformance with I=B=R code, and said ratings have been approved by the I=B=R
Baseboard Rating committee.
1" Copper/Aluminum
Single element Panel-Trim AHC hot water ratings BTU per hour per linear foot
of active (finned) length.
AVERAGE WATER TEMPERATURE
Degrees F
150°
160°
170°
180°
190°
200°
210°
220°
Rated Capacity
1GPM
480
560
650
730
820
900
980
1070
4GPM
510
590
690
770
870
950
1040
1130
The use of I=B=R Rating @ 4GPM is limited to installations where flow rate is known
to be equal to or greater than 4 GPM. If flow rate is unknown, use 1 GPM rating
· I=B=R Ratings include 15% addition to water heat capacity · Hot water
ratings shown are at the STANDARD WATER FLOW RATE of 500 lbs/hr (1GPM) and 2,000 lbs/hr
(4 GPM) with 65° entering air temperature · Friction loss through Argo
Baseboard unit at 1 GPM (500 lbs/hr) is 13 MIL-INCHES per foot and at 4 GPM (2000 lbs/hr)
is 145 MIL-INCHES PER FOOT · Ratings based on active length. Difference between
active and total length is approximately 2". Aluminum fins are 2-1/8" x
2-¾" x .011" thick, spaced 60 per foot (unpainted) · All hot
water ratings shown in this table determined in conformance with I=B=R code, and said
ratings have been approved by the I=B=R Baseboard Rating committee.
1¼" IPS Steel or Copper/Aluminum
Single fintube. BTU per hour per linear foot of active (finned) length.
Manufacturer's rating.
AVERAGE WATER TEMPERATURE
Degrees F
160°
170°
180°
190°
200°
210°
220°
Rated Capacity
1GPM
417
482
546
612
676
741
806
Fin size 2-¾" x 3-¾" x .016" steel, 40 fins/ft. painted
black · Fin tube weight 3.5 lbs. per foot · Pitch: Maximum 1/8"
per foot Minimum 10 foot length ¼" Consult manufacturer for
1-¼" Copper/Aluminum data.
Argo Baseboard
260 North Elm St.
Westfield, MA 01085
Phone: 413-568-9571
Fax: 413-572-3764