Panel-Trim Baseboard Radiation
Providing comfort to any room with style!

Features   ·   Accessories   ·   Statistics


¾" Copper/Aluminum
Single element Panel-Trim AAA-3 hot water ratings BTU per hour per linear foot of active (finned) length.
AVERAGE WATER TEMPERATURE
Degrees F   150° 160° 170° 180° 190° 200° 210° 220°
Rated
Capacity
1GPM 480 570 650 740 820 910 990 1080
4GPM 510 600 690 780 870 960 1050 1140
The use of I=B=R Rating @ 4GPM is limited to installations where flow rate is known to be equal to or greater than 4 GPM. If flow rate is unknown, use 1 GPM rating · I=B=R Ratings include 15% addition to water heat capacity · Hot water ratings shown are at the STANDARD WATER FLOW RATE of 500 lbs/hr (1GPM) and 2,000 lbs/hr (4 GPM) with 65° entering air temperature · Friction loss through Argo Baseboard unit at 1 GPM (500 lbs/hr) is 47 MIL-INCHES per foot and at 4 GPM (2000 lbs/hr) is 525 MIL-INCHES PER FOOT · Ratings based on active length. Difference between active and total length is approximately 2". Aluminum fins are 2-1/8" x 2-¾" x .008" thick, spaced 60 per foot (unpainted) · All hot water ratings shown in this table determined in conformance with I=B=R code, and said ratings have been approved by the I=B=R Baseboard Rating committee.


1" Copper/Aluminum
Single element Panel-Trim AHC hot water ratings BTU per hour per linear foot of active (finned) length.
AVERAGE WATER TEMPERATURE
Degrees F   150° 160° 170° 180° 190° 200° 210° 220°
Rated
Capacity
1GPM 480 560 650 730 820 900 980 1070
4GPM 510 590 690 770 870 950 1040 1130
The use of I=B=R Rating @ 4GPM is limited to installations where flow rate is known to be equal to or greater than 4 GPM. If flow rate is unknown, use 1 GPM rating · I=B=R Ratings include 15% addition to water heat capacity · Hot water ratings shown are at the STANDARD WATER FLOW RATE of 500 lbs/hr (1GPM) and 2,000 lbs/hr (4 GPM) with 65° entering air temperature · Friction loss through Argo Baseboard unit at 1 GPM (500 lbs/hr) is 13 MIL-INCHES per foot and at 4 GPM (2000 lbs/hr) is 145 MIL-INCHES PER FOOT · Ratings based on active length. Difference between active and total length is approximately 2". Aluminum fins are 2-1/8" x 2-¾" x .011" thick, spaced 60 per foot (unpainted) · All hot water ratings shown in this table determined in conformance with I=B=R code, and said ratings have been approved by the I=B=R Baseboard Rating committee.


1¼" IPS Steel or Copper/Aluminum
Single fintube. BTU per hour per linear foot of active (finned) length.
Manufacturer's rating.
AVERAGE WATER TEMPERATURE
Degrees F   160° 170° 180° 190° 200° 210° 220°
Rated
Capacity
1GPM 417 482 546 612 676 741 806
               
Fin size 2-¾" x 3-¾" x .016" steel, 40 fins/ft. painted black · Fin tube weight 3.5 lbs. per foot · Pitch: Maximum 1/8" per foot Minimum 10 foot length ¼" Consult manufacturer for 1-¼" Copper/Aluminum data.


close box