Lo-Trim Baseboard Radiation
Providing comfort to any room with style!

Features   ·   Accessories   ·   Statistics

Single Element Lo-Trim Hot Water Ratings BTU per hour per linear foot of active (finned) length (with damper).
AVERAGE WATER TEMPERATURE
Degrees F   150° 160° 170° 180° 190° 200° 210° 220°
Rated
Capacity
1GPM 370 430 500 560 630 690 760 820
4GPM 390 450 530 590 670 730 800 870
The use of I=B=R Rating @ 4 GPM is limited to installations where flow rate is known to be equal to or greater than 4 GPM. If flow rate is unknown, use 1 GPM rating.

I=B=R Ratings include 15% addition to water heat capacity.

Hot water ratings shown are at the STANDARD WATER FLOW RATE of 500 lb/hr (1 GPM) and 2,000 lbs/hr (4 GPM) with 65° entering air temperature.

Rating base on active length. Difference between active and total length is 3".

Aluminum fins are 2 11/32" x 1 7/8" x .008" thick, spaced 65 per foot (unpainted).

All hot water ratings shown in this table determined in conformance with I=B=R Baseboard Rating commitee.

close box